UPONOR CONTROL SYSTEM KNX INTERFACE MANUAL - CONNECTING UPONOR CONTROLLER C-56 WITH MEDIA COUPLER TR131A/B
7
5 Uponor Controller C-56 Radio data point lists
5.1 Data point list per zone
Parameter name Explanation KNX data type Display condition Read
only
Limited
write
access
Full
access
Room
Temperature Info
Measured room temperature. Can be supplied
by Uponor Thermostats or other KNX devices.
DPT_Value_Temp R R R/W
Room Setpoint
Local Info
Local room setpoint. Can be set in Uponor
thermostats or other KNX devices.
DPT_Value_Temp R R R/W
Remote Setpoint Remote room setpoint. Can be used to override
the local setpoint.
DPT_Value_Temp R R R/W
Min Room
Setpoint
Setpoint limitation DPT_Value_Temp R R R/W
Max Room
Setpoint
Setpoint limitation DPT_Value_Temp R R R/W
Floor Temperature Measured floor temperature. Can be supplied
by Uponor Thermostat T-54 or other KNX
devices.
DPT_Value_Temp Valid if sensor is
linked
RR R/W
Min Floor
Temperature
Local minimum limitation for floor
temperature. Can be set in Uponor Thermostat
T-54.
DPT_Value_Temp Valid if sensor is
linked
RR R/W
Max Floor
Temperature
Local maximum limitation for floor
temperature. Can be set in Uponor Thermostat
T-54.
DPT_Value_Temp Valid if sensor is
linked
RR R/W
Remote Min Temp
Floor
Remote minimum limitation for floor
temperature. Can be used to override the local
limit.
DPT_Value_Temp Valid if sensor is
linked
RR R/W
Remote Max
Temp Floor
Remote maximum limitation for floor
temperature. Can be used to override the local
limit.
DPT_Value_Temp Valid if sensor is
linked
RR R/W
Battery Status 0 = Not OK, 1 = OK DPT_BinaryValue R R R
Radio Status 0 = Not OK, 1 = OK DPT_BinaryValue R R R
Actuator Status 0 = Closed, 1 = Open DPT_BinaryValue R R R
Actuator Alarm 0 = Not OK, 1 = Alarm DPT_Alarm R R R
Actuator Cycle Cycle counter DPT_Value_4_
Ucount
RR R
Status Call Active if heating or cooling needed DPT_Switch R R R
Min Output Power Minimum limitation for parameter Output
power. Can be set in MMI in Service mode or
via KNX.
DPT_Scaling Valid if auto
balancing is active
RR R/W
Max Output
Power
Maximum limitation for parameter Output
power. Can be set in MMI in Service mode or
via KNX.
DPT_Scaling Valid if auto
balancing is active
RR R/W
Comfort Setting Background heating. Can be set in MMI in
Installer mode or via KNX.
DPT_Scaling R R R/W
Output Power The used output power level DPT_Scaling Valid if auto
balancing is active
RR R
Outdoor
Temperature
Outdoor temperature from external sensor via
Uponor Thermostat T-54
DPT_Value_Temp Valid for all channels
if one outdoor
sensor is linked
RR R/W